3rd Edition of TEMI880 IM : Aug. 22. 2005 Page 16 / 123
1.4.2.9 Auxiliary Relay
If contact capacity is over 250VAC – resistance load 5A, 30VDC – resistance load 5A,
use auxiliary relay for ON/OFF load.
If you INDUCTANCE(L) load like as AUXILIARY RELAY or SOLENOIDE VALVE, It might make go to wrong
or out of order relay, please make sure insert to parallel circuit with CR FILTER(AC) or DIODE(DC) by
SURGE SUPPRESSOR of avoiding sparks.
Recommend CR FILTER
Sung Ho Electronics : BSE104R120 25V (0.1μ+120Ω)
HANA PARTS CO. : : HN2EAC
Songmi Electric Co., Ltd. :: CR UNIT 953, 955 etc
Jiwol Electric Co., Ltd. : : SKV, SKVB etc
Shinyoung Communication Co., Ltd. :: CR-CFS, CR-U etc
DC RELAY
AC RELAY
CAUTION
Out DC Power
Machine
R
DIODE
(Connect Relay Coil socket directly)
RELAY
(Use what a rated Relay Coil is must
be less than contact point capacity)
Out AC power
Machine
R
CR FILTER
(Connect Relay Coil socket directly)
RELAY
(Use what a rated Relay Coil is must
be less than contact point capacity)